Program run by City of Orlando Public Works, Water Reclamation Division (Oil & Grease Management Program, City Code §30.15). Hand-checked against source Last verified 2026-10-19 by Stew Israil, GreaseTrapRules. Report an error / rule changed

Quick answer

From the official source(s) below, last checked 2026-10-19. Rules change; verify with your city.

Am I compliant in Orlando?

Six quick questions, checked against Orlando's sourced rules. Nothing is saved.

Free printable cleaning log & inspection checklist for Orlando

Get grease trap pumping quotes in Orlando, FL

Tell us what you need and we'll send your request to the Featured grease trap service companies in Orlando, FL, with a copy to us. If there are none yet, it comes only to us and we may reply to help you find someone. Free, no obligation. For restaurants and for property, building and facility managers.

We don't sell your details. See our Privacy Policy and Terms of Service.

Rules change; verify with your city. Summaries are plain-English restatements of the official source linked below; “Source says” shows the exact wording. Blank rows mean the sources we checked did not state that rule, not that there is no rule.

Orlando grease trap rules at a glance

Grease trap and FOG (fats, oils and grease) rules for restaurants in Orlando are set by City of Orlando Public Works, Water Reclamation Division (Oil & Grease Management Program, City Code §30.15). Pumping: at least every 90 days (under-sink traps weekly). A FOG or wastewater permit is required. Keep pumping records or manifests on site for inspectors.

Of the 5 Florida programs we track, 4 state a pumping schedule and 3 require a permit. We have not verified a pumping company for Orlando yet; see Florida pumping companies. Compare all Florida cities.

Florida statewide rule: grease waste haulers and service manifests (F.S. 403.0741)

Source: Florida Statutes § 403.0741, Grease waste removal and disposal · checked 2026-10-18

Orlando grease trap & interceptor rules, line by line

Required trap / interceptor type
Food establishments need an approved grease interceptor. Under-sink interceptors are not allowed for new facilities.
✓ checked against source
Sizing rule
Interceptors are sized case by case under the City of Orlando Engineering Standards Manual.
✓ checked against source
Pumping / cleaning frequency
Grease interceptors must be completely pumped out at least every 90 days; the Director can set a shorter interval but never longer than 90 days. Under-sink grease traps must be cleaned weekly.
✓ checked against source
Permit required?
An Oil & Grease Management Program discharge certificate is required. It is valid for up to 5 years; apply to renew at least 60 days before it expires. Program fees are billed on the water/sewer bill.
✓ checked against source
Permit & program feesNot stated in the sources we checked
Inspections
The City inspects interceptors. A unit is out of compliance if the grease layer is over 6 inches and solids over 12 inches, or removal efficiency is under 80%; violations get a notice with 72 hours to correct.
✓ checked against source
Record keeping
Keep a 12-month pumping log posted on site (date, time, volume pumped, hauler name, license and signature) plus a file with as-builts, inspection reports and receipts. Pumpings must be reported to the City within 48 hours, with a manifest. Decanting (returning gray water to the interceptor) is not allowed (Florida s. 403.0741).
✓ checked against source
Pumper / hauler approvalNot stated in the sources we checked
Reporting portalNot stated in the sources we checked
Fines & penaltiesNot stated in the sources we checked
Program contact
407.246.3922
407.246.3086
✓ checked against source

Sources

Grease trap cleaning & pumping companies in Orlando, FL

No verified pumping company for Orlando yet. Free listings are sorted A–Z. A listing is not an endorsement.

Before you book: ask for a full pump-out (not a skim) and a signed manifest for every service, and keep it on site for inspectors.

Try the Florida pumper list for companies serving nearby cities.

All Florida pumpersNational directoryRun a pumping company? List it free

Size your interceptor

Use the grease interceptor sizing calculator (UPC, IPC and PDI methods), then confirm Orlando's own minimums above. Not sure how often to pump? Read how often to pump a grease trap.

Orlando grease trap FAQ

How often do grease traps have to be pumped in Orlando, FL?

Pump at least every 90 days (under-sink traps weekly). Source: City of Orlando Public Works, Water Reclamation Division (Oil & Grease Management Program, City Code §30.15), checked 2026-10-19. Rules change; confirm with the local sewer authority.

Do restaurants in Orlando need a grease trap permit?

Oil & grease discharge certificate required, per the official source checked 2026-10-19.

Who enforces grease trap rules in Orlando, FL?

City of Orlando Public Works, Water Reclamation Division (Oil & Grease Management Program, City Code §30.15) (program contact: 407.246.3922 · 407.246.3086). Contact them for permits, inspections and approved haulers.

Nearby Florida cities

JacksonvilleMiamiSt. PetersburgTampa

Grease trap guides

For property and building managersTenant vs landlord, shared interceptors, recordsHow often to pumpThe 25% rule and city schedulesFOG inspection checklistWhat inspectors checkPrintable maintenance logPlus record-keeping rulesAll guidesSizing, trap vs interceptor, cost factors
Get quotes

Grease rule changes, once a week

A short email when a city changes its FOG ordinance, pumping schedule, permit fees or reporting portal. Free.